HAN Shaigen, CAO Bin, HUANG Qiang, et al. Electric Field Analysis and Shielding Optimization of 40.5 kV Wall Bushing[J]. High VoltageApparatus, 2017, 53(1): 113-118.
HAN Shaigen, CAO Bin, HUANG Qiang, et al. Electric Field Analysis and Shielding Optimization of 40.5 kV Wall Bushing[J]. High VoltageApparatus, 2017, 53(1): 113-118. DOI: 10.13296/j.1001-1609.hva.2017.01.019.
Electric Field Analysis and Shielding Optimization of 40.5 kV Wall Bushing
This paper is aimed at the problem that the busbar bushing of 40.5 kV switchgear is prone to local aging
the Ansys Workbench software is used to analyze the electric field of the wall bushing and find the concentrated position of the electric field.The method of using a single potential shield loop or high potential and ground potential shield ring combination to solve the local electric field concentration problem of the wall bushing is proposed in this paper. Also the effects of the size and size of the shield ring on the electric field distribution of the wall bushing are analyzed.In this paper
b=15 mm
c=27.6 mm
d=17 mm
e=25 mm
and the maximum elec-tric field value of the air field in each case is calculated and the curve is plotted. Through a lot of simulation verification and data screening
under the power frequency withstand voltage
the field strength of the air around the casing wall is E =2.61 ×106V/m.The design of the lower cost
the electric field is better optimized with high
ground potential shielding of the wall bushing
effectively improve the wall around the casing wall electric field distribution
improve the insulation level of the wall bushing
effectively solve the problem of insufficient insulation capability of the busbar insulation sleeve of switchgear
and improve the reliability of equipment operation.