CHE Bin, ZHANG Liang, LI Junhao, et al. Voltage Distributions in 220 kV GIS Under Oscillatory Lightning Impulse and Standard Lightning Impulse[J]. High voltageapparatus, 2017, 53(2): 125-131.
CHE Bin, ZHANG Liang, LI Junhao, et al. Voltage Distributions in 220 kV GIS Under Oscillatory Lightning Impulse and Standard Lightning Impulse[J]. High voltageapparatus, 2017, 53(2): 125-131. DOI: 10.13296/j.1001-1609.hva.2017.02.020.
Voltage Distributions in 220 kV GIS Under Oscillatory Lightning Impulse and Standard Lightning Impulse
GIS(gas insulated switchgear)is widely used in power system for its excellent performance. Insulation assessment of GIS by standard impulse is performed in factory
whereas oscillating impulse is adopted in field test.The distribution of voltage on the nodes inside GIS induced by oscillating impulse or standard impulse is the basis for test result analysis. To understand the voltage distribution under the two impulses
this paper adopts the numerical simulation software ATP-EMTP to simulate the wave propagations in a 220 kV GIS
and the voltages on internal nodes induced by the two impulses are obtained and compared. The results show that there will be higher overvoltage under standard lightning impulse than that under oscillating lightning impulse. With the increase of distance between measuring point and entrance
the voltage on node drops and its distortion decreases. This study would provide data support for the choice of field test scheme and insulation evaluation of GIS.