LIU Qing, WANG Le, LIU Peng. Measurement of Radiation Electric Field Produced by Action of GIS Circuit Breaker[J]. High voltageapparatus, 2017, 53(2): 166-171.
LIU Qing, WANG Le, LIU Peng. Measurement of Radiation Electric Field Produced by Action of GIS Circuit Breaker[J]. High voltageapparatus, 2017, 53(2): 166-171. DOI: 10.13296/j.1001-1609.hva.2017.02.026.
Measurement of Radiation Electric Field Produced by Action of GIS Circuit Breaker
Operations of switches in GIS will cause very fast transient overvoltage(VFTO)
which can induce transient radiation electric field. By the mode of conduction or radiation
the secondary equipment may be disturbed or even permanently damaged. In order to find the different characteristics of E-field amplitude and frequency of different voltage
a set of fiber measurement system meeting the required is built up and the calibration test is carried out. The E-fields caused by one 1 100 kV and one 550 kV singe-phase GIS breaker are measured.The result shows:the higher the voltages level
the higher the radiation electric field pulse amplitudes
and the more pulse numbers. The amplitudes of 550 kV GIS and 1 100 kV GIS are 0.13 kV/m and 0.75 kV/m respectively. The main frequency distribution range is widened with the voltage increase.