ZHANG Yiming, LI Shaohua, JIN Guangyao, et al. Research of the Effect of Electromagnetic Interference on Secondary Equipment in High Voltage Switchgear[J]. High voltageapparatus, 2017, 53(2): 191-198.
ZHANG Yiming, LI Shaohua, JIN Guangyao, et al. Research of the Effect of Electromagnetic Interference on Secondary Equipment in High Voltage Switchgear[J]. High voltageapparatus, 2017, 53(2): 191-198. DOI: 10.13296/j.1001-1609.hva.2017.02.030.
Research of the Effect of Electromagnetic Interference on Secondary Equipment in High Voltage Switchgear
Popularization and application of smart primary equipment in Smart Substation
introduces plenty of secondary equipments for power system
which operate in strong electromagnetic interference environment produced by primary equipment
and are easily affected by strong interference of primary equipment and failure. Transient ground potential rise(TGPR)caused by operating disconnector
produces higher overvoltage magnitude
and larger interference for secondary equipment. In this paper we measure the electromagnetic interference caused at signal line of secondary equipment during disconnector switching bus charging current of 252 kV intelligent GIS
and the analysis indicates:TEV may cause higher coupling voltage
measured value is over 1 kV in test
may give rise to malfunction or fault of secondary equipment;Adopting surge protective device to absorb voltage traveling wave
can effectively reduce positive and negative maximum voltage amplitude