BI Yinghua, LI Haomin, HAN Guiquan, et al. Study on the Characteristics of High Current Arc of 3/4 Turn Coil-type AMF Contact in 126 kV Vacuum Interrupter[J]. High voltageapparatus, 2017, 53(3): 35-40.
BI Yinghua, LI Haomin, HAN Guiquan, et al. Study on the Characteristics of High Current Arc of 3/4 Turn Coil-type AMF Contact in 126 kV Vacuum Interrupter[J]. High voltageapparatus, 2017, 53(3): 35-40. DOI: 10.13296/j.1001-1609.hva.2017.03.005.
Study on the Characteristics of High Current Arc of 3/4 Turn Coil-type AMF Contact in 126 kV Vacuum Interrupter
The objective of this paper is to experimentally determine the coil width of a 3/4 coil-type axial magnetic field(AMF) contact used in 126 kV vacuum interrupters by comparing the duration of diffuse arc mode
duration of intense arc mode and high current vacuum arc behavior. Three types of coil width are tested in the experiment. The coil width of contact type 1
contact type 2 and contact type 3 is 12 mm
14 mm and 16 mm
respectively. Arc current is set as 36 kA(rms) and 40 kA(rms). Arc duration in first current half-wave is set as3.5 ms and 9 ms. Experiment results show that the duration of diffuse arc mode before current zero of contact type 2 is the longest among the 3 types of contact. The duration of intense arc mode of contact type 2 is the shortest among the 3 types of contact. Besides
with the increase of arc current
the duration of diffuse arc mode before second current zero of each type of contact decreases. Based on the experiment results
the coil width of the 3/4 coil-type contact used in 126 kV vacuum interrupter is determined as 14 mm.
Simulation Analysis on Influence of Current Frequency on Breaking Capacity of Vacuum Circuit Breaker
Vacuum Arc Ignition and Ablation Characteristics of CuCr55 Electrode Contacts
The Influence of Axial Magnetic Field on Charged Particle Density in Vacuum Arc…
A System to Detect the Light Emission of Vacuum Arc
The Way to Measure the Distribution of Electron Density for Vacuum Arc by Double Array Probes
Related Author
DING Can
CHEN Lixue
YUAN Zhao
LI Kaiming
XIE Hongtao
LIU Siyuan
BO Xianglai
WANG Xiaojun
Related Institution
State Key Laboratory of Advanced Electromagnetic Engineering and Technology, School of Electrical and Electronic Engineering, Huazhong University of Science and Technology
Hubei Transmission Line Engineering Technology Research Center, China Three Gorges University
College of Electrical Engineering & New Energy, China Three Gorges University
Shaanxi Baoguang Vacuum Electric Device Co., Ltd.
School of Electrical Engineering, Xi'an Jiaotong University