LUO Shicong, FAN Jie, HOU Yufei, et al. Eliminating Method for the Conductor Induced Additional Voltage Drop in the Arc Voltage Measurement of High Voltage Circuit Breakers[J]. High voltageapparatus, 2017, 53(3): 64-68.
LUO Shicong, FAN Jie, HOU Yufei, et al. Eliminating Method for the Conductor Induced Additional Voltage Drop in the Arc Voltage Measurement of High Voltage Circuit Breakers[J]. High voltageapparatus, 2017, 53(3): 64-68. DOI: 10.13296/j.1001-1609.hva.2017.03.010.
Eliminating Method for the Conductor Induced Additional Voltage Drop in the Arc Voltage Measurement of High Voltage Circuit Breakers
Arc voltage measurement is an important method to study the characteristics of breaking arc. To eliminate the voltage drop caused by the inner conductors of high voltage circuit breakers
in this paper
an eliminating method of the additional pressure drop is proposed
and an arc voltage measurement device is developed. Experimental results show that the arc voltage measurement device is suitable for the rated voltage of12
1
26 kV high voltage circuit breakers. Furthermore
the measurement of arc voltage by using the proposed method is efficient and convenient comparing with the existing methods that need an additional test with short circuit current passing through the test objects.