LI Min, LI Da, WANG Xiaoqin. Effect of Rabbet Assembly Position of Moving and Static Contacts on Performance of Vacuum Interrupter[J]. High voltageapparatus, 2017, 53(3): 106-111.
LI Min, LI Da, WANG Xiaoqin. Effect of Rabbet Assembly Position of Moving and Static Contacts on Performance of Vacuum Interrupter[J]. High voltageapparatus, 2017, 53(3): 106-111. DOI: 10.13296/j.1001-1609.hva.2017.03.017.
Effect of Rabbet Assembly Position of Moving and Static Contacts on Performance of Vacuum Interrupter
To understand the effect of rabbet assembly position of moving and static contacts on performance of vacuum interrupter
simulation and experimental methods were employed to analyze the performance of a vacuum interrupter with different rabbet assembly position
and the effects of rabbet assembly position on magnetic flux density and arc pattern were obtained. The results showed that when the dislocation degree of rabbet was 45°
the maximum value of magnetic flux density was 63.71
64.31 and 64.18 mT
respectively; the arc had smaller size
more stable movement
and the voltage of 36 V; and the interruption performance of the vacuum interrupter was better. So it is concluded that the interruption performance of the vacuum interrupter can be improved at 45° dislocation of rabbet in assembly.