Electromagnetic Transient Study and Equipment Selection of Neutral Current-limiting Reactor Installation for Main Transformer in 500 kV Luoping Substation
|更新时间:2025-04-26
|
Electromagnetic Transient Study and Equipment Selection of Neutral Current-limiting Reactor Installation for Main Transformer in 500 kV Luoping Substation
High VoltageApparatusVol. 53, Issue 5, Pages: 170-174(2017)
WANG Dianlang, LI Dong, YANG Xiaowei, et al. Electromagnetic Transient Study and Equipment Selection of Neutral Current-limiting Reactor Installation for Main Transformer in 500 kV Luoping Substation[J]. High voltageapparatus, 2017, 53(5): 170-174.
WANG Dianlang, LI Dong, YANG Xiaowei, et al. Electromagnetic Transient Study and Equipment Selection of Neutral Current-limiting Reactor Installation for Main Transformer in 500 kV Luoping Substation[J]. High voltageapparatus, 2017, 53(5): 170-174. DOI: 10.13296/j.1001-1609.hva.2017.05.027.
Electromagnetic Transient Study and Equipment Selection of Neutral Current-limiting Reactor Installation for Main Transformer in 500 kV Luoping Substation
the medium voltage side of the autotransformer reactance is very close to zero
leading to fault ride through current is close to or even exceed the transformer can withstand short circuit current limit value when nearly single-phase or two-phase grounding transformer 220 kV side
to restrict Luoping Substation 220 kV single phase or two phase short circuit current level
improve the main transformer running environment
in main transformer neutral point reactor with current limit. Using the latest EMTPE program
the electromagnetic transient characteristics of the main transformer
such as the level of the main transformer current
overvoltage
insulation and so on
are studied. It is put forward that the 500 kV main transformer neutral point Luoping Substation current-limiting reactor impedance selection principle
current-limiting effect
power frequency and switching overvoltage level
steady state and transient current level on the neutral point reactor of main transformer
the main transformer neutral arrester and current limiting reactor technology parameters are determined. By means of the transformation
it can significantly reduce the level of 220 kV single or two phases short-circuit current in Luoping Substation
and improve the operating condition of the main transformer.