LI Kun, SHAO Mingxin, WANG Benjin, et al. On-line Monitoring System for ±1 100 kV DC Voltage Transformer[J]. High voltageapparatus, 2017, 53(6): 1-7. DOI: 10.13296/j.1001-1609.hva.2017.06.001.
On-line Monitoring System for ±1 100 kV DC Voltage Transformer
UHVDC voltage transformer connects the primary transmission line and the control protection devices on secondary side.Its working state directly affects the operation performance of UHVDC system.So on-line monitoring is important for UHVDC voltage transformer ’ operation and maintenance.The experience from field operation shows that lightning disturbance
transformer flashover and capacitor breakdown are the key factors affecting the working condition of UHVDC voltage transformer.In this study
simulation and measurement are adopted to analyze the above three monitoring features
and a ±1 100 kV DC voltage transformer on-line monitoring system
including a multi-sensor and multi-feature extraction module and a fault waveforms storage and judgment module
is designed.Moreover
the transient performance of the designed air-core coil sensor is tested
and the measured waveform agrees well with the standard one.