ZHANG Xuesong, LU Zhicheng, ZHU Zhubing. Establishment and Validation of Finite Element Model of Seismic Action for Interconnected UHV Equipment in Substation[J]. High voltageapparatus, 2017, 53(6): 25-29.
ZHANG Xuesong, LU Zhicheng, ZHU Zhubing. Establishment and Validation of Finite Element Model of Seismic Action for Interconnected UHV Equipment in Substation[J]. High voltageapparatus, 2017, 53(6): 25-29. DOI: 10.13296/j.1001-1609.hva.2017.06.005.
Establishment and Validation of Finite Element Model of Seismic Action for Interconnected UHV Equipment in Substation
To build a seismic finite element model of the interconnected UHV equipment
the characteristic parameters of restoring force of the sliding fittings for hard bus and the bit-shaped function of flexible bus considering stiffness
must be determined.In this study
quasi-static test was conducted to obtain the restoring force parameters of the sliding fittings
such as the sliding force
the sliding stiffness
and the additional damping ratio.And the bit-shaped function considering the stiffness of flexible bus was deduced via mechanical analysis.Thus
a seismic finite element model of the interconnected UHV equipment was established.Finite element analysis shows that the calculation results of the interconnected UHV equipment are very close to the test data of shaking table
which validates the correctness of the finite element model.This study may provide theoretical and experimental foundation for establishing finite element model of interconnected UHV equipment.