Influence of Lowering Rated Voltage or Residual Voltage of MOA on Canceling the Pre-insert Closing Resistor in 750 kV Circuit Breaker
the 750 kV projects in northwest region of China usually are equipped with the MOAs with rated voltage of 600 kV at bus bar side and 648 kV at transmission line side.Almost all the circuit breakers in the 750 kV transmission lines have pre-inset closing resistors
which resistance is 570
6
00 Ω.According to the research on the differentiation of the power frequency overvoltage
the rated voltage of MOA at both bus bar side and line side can be further reduced in a certain range.Improvement of MOA performance can lower the closing overvoltage
accordingly the residual voltage of MOA will reduce
wh
ich is in favor of canceling the closing resistor.In this paper
the closing overvoltage after reduction of the rated voltage or residual voltage of the MOA for 750 kV projects is investigated.Based on the calculation of the flashover rate due to closing overvoltage
the application range of canceling the closing resistor is suggested.