WANG Chengjia, TANG Li, LI Xinwei, et al. Effect of Metallic Particles on Electric Field of AC Filter Circuit Breaker Arc-extinguishing Chamber[J]. High voltageapparatus, 2017, 53(6): 105-112.
WANG Chengjia, TANG Li, LI Xinwei, et al. Effect of Metallic Particles on Electric Field of AC Filter Circuit Breaker Arc-extinguishing Chamber[J]. High voltageapparatus, 2017, 53(6): 105-112. DOI: 10.13296/j.1001-1609.hva.2017.06.018.
Effect of Metallic Particles on Electric Field of AC Filter Circuit Breaker Arc-extinguishing Chamber
several explosion cases have taken place in convertor stations due to continually breaking operation of AC filter circuit breaker
which brings a huge threat to the stability and reliability of the network.Preliminary analysis shows that switching current of AC filter circuit breaker leads to arcing contact burning
producing some metallic particles.These particles may cause the electric field distortion of the arc-extinguishing chamber and reduce the insulation strength of the equipment.To solve the problem
the research on the influence that the metallic particles bring to the electric field of arc-extinguishing chamber in ACF circuit breakeris carried out.First
the model of both 550 kV ACF circuit breaker chamber and metallic particles is built by means of Solidworks and Ansys based on the theory of numerical analysis of electromagnetic fields
and the field distribution without metallic particles is simulated and analyzed.Then
the effect of shape and radius of the metallic particles on the field distribution
and the effect of different locations on insulation strength are analyzed.It suggests that metallic particles add up the maximum electric field strength of breaker chamber
and the shape of particle causes discrepancy to the calculating result.With the radius of hemispherical particle increasing
the maximum field strength reduces.In addition
when the particle is located on the surface of static arcing contact
the influence reaches the maximum.Finally
the influence of breaking parameter on the electric field is analyzed
and the preliminary optimizing advice is proposed
that is
improving the minimum arcing time to 5 ms
so that the maximum electric field strength will be lower than the SF6 gas engineering breakdown field strength.