PENG Chenyi, JIN Lijun, ZHANG Yingyao. Exposure Assessment of Non-uniform Electromagnetic Filed Based on Realistic Human Model[J]. High voltageapparatus, 2017, 53(6): 161-166.
PENG Chenyi, JIN Lijun, ZHANG Yingyao. Exposure Assessment of Non-uniform Electromagnetic Filed Based on Realistic Human Model[J]. High voltageapparatus, 2017, 53(6): 161-166. DOI: 10.13296/j.1001-1609.hva.2017.06.027.
Exposure Assessment of Non-uniform Electromagnetic Filed Based on Realistic Human Model
staffs in electric utility need to work long time under high level electromagnetic field.However
excessive exposure will harm human health.Therefore
exposure assessment of electromagnetic field is very important in the development of new energy technologies.For the current exposure assessment methods
the calculation cost of voxel human model is very high
and insufficient attention is paid to the non-uniform electromagnetic field in real working condition.This paper proposes two practical methods for assessing the exposure of non-uniform electromagnetic fields.A realistic human body model is established
and the correctness of the model is verified.Equivalent uniform electromagnetic field is obtained by comparing the maximum electromagnetic field level which people is exposed to and the corresponding induced electric field in human body.The spatial average of exposure through the whole body is determined by arithmetic mean averaging and quadratic mean averaging
respectively.An assessment example of non-uniform magnetic field exposure around air-core reactor is given to demonstrate the effectiveness of the equivalent uniform electromagnetic field approach and the spatial averaging approach in assessing non-uniform exposure based on realistic human body model.