Research on Electric Field Distribution Characteristics of Body Surface with Live Working in Compact 500 kV Same Tower Double Circuit Transmission Lines
|更新时间:2025-04-26
|
Research on Electric Field Distribution Characteristics of Body Surface with Live Working in Compact 500 kV Same Tower Double Circuit Transmission Lines
High VoltageApparatusVol. 53, Issue 7, Pages: 87-94(2017)
LIU Xiaqing, WU Dong, LI Hui, et al. Research on Electric Field Distribution Characteristics of Body Surface with Live Working in Compact 500 kV Same Tower Double Circuit Transmission Lines[J]. High voltageapparatus, 2017, 53(7): 87-94.
LIU Xiaqing, WU Dong, LI Hui, et al. Research on Electric Field Distribution Characteristics of Body Surface with Live Working in Compact 500 kV Same Tower Double Circuit Transmission Lines[J]. High voltageapparatus, 2017, 53(7): 87-94. DOI: 10.13296/j.1001-1609.hva.2017.07.014.
Research on Electric Field Distribution Characteristics of Body Surface with Live Working in Compact 500 kV Same Tower Double Circuit Transmission Lines
The electric field protection is an important part of live working security technology research
which related to the workers’ safety. This article purposefully analyzes the structural characteristics of compact 500 k V same tower double circuit transmission lines
establishes the simulation model of body surface field strength
and calculates the body surface field strength of different operating points under typical conditions. At the same time
it analyzes the influence of the tower type and line operation mode on body surface field strength distribution. The results show that: under the same operating mode
when working at ground potential
the head and foot field strengths of the personnel working in the linear tower are about 4 times higher than those in the strain towers; When working in equipotential
the head field strength on the strain towers is 243.2 k V/m higher than that in the linear towers
and hand field strength is 1.9 times higher than that in the linear towers. When working in the same tower
compared with one circuit operation mode
two circuit operation modes under the same conditions has a stronger influence on the equipotential operation;When working in ground potential
the influence of the operation mode on the body surface field strength on the cross arm is obvious. Through the calculation of shielding efficiency
the safety protection measures under different working conditions and different operation points are checked. The research results can provide theoretical reference for safety protection of live working
Simulation Analysis of Electric Field on Live Working of ±800 kV Transmission Line
Research on Human Digital Twins for Live Working on Transmission Lines Based on Attitude Estimation
Study on the Amplitude and Energy Characteristics of the in and out of Equipotential Pulse Current for 1000 kV Transmission Line Tension Tower Based on HHT
Live Working Insulation Blanket Surface Defect Recognition Based on Improved YOLOv8
Insulation Protection Design of Live working Robot for 10 kV Distribution Power Systems
Related Author
PAN Junwen
LUO Richeng
PAN Qianwen
ZHANG Chengwu
XU Jinshuai
WANG Wei
MA Aiqing
WU Tian
Related Institution
Suizhou Power Supply Company,State Grid Hubei Electric Power Company
School of Electrical and information Engineering, Changsha University of Science & Technology
School of Electrical Engineering, Shanghai University of Electric Power