ZHANG Jinbo, GAO Xiangxiang, ZHANG Yunfei, et al. Calculation and Study of TRV Parameters for Asymmetric Short-circuit Breaking Test(T100a) Based on Current Injection Method[J]. High voltageapparatus, 2017, 53(7): 95-99.
ZHANG Jinbo, GAO Xiangxiang, ZHANG Yunfei, et al. Calculation and Study of TRV Parameters for Asymmetric Short-circuit Breaking Test(T100a) Based on Current Injection Method[J]. High voltageapparatus, 2017, 53(7): 95-99. DOI: 10.13296/j.1001-1609.hva.2017.07.015.
Calculation and Study of TRV Parameters for Asymmetric Short-circuit Breaking Test(T100a) Based on Current Injection Method
When the high-voltage AC circuit-breakers breaking the asymmetrical short-circuit fault in the power system
the short-circuit current is the superposed by AC component and DC component which resulting the last current arc-extinguishing loop is major loop or minor loop. Because the current zero point deviates from peak of the power supply voltage
the TRV peak will be lower than the value of symmetrical short circuit fault breaking. Based on the principle of current injection and TRV values of T100 s
according to current expression of T100 s and T100 a
the correction coefficients of TRV values of T100 a can be calculated for major loop or minor loop. Finally
the research of this paper can help to assess the TRV parameters of T100 a test and adjust the R
L
C values of frequency modulation device in high power laboratory.