Early Warning Strategies of the Dielectric Loss Monitoring for Transformer Bushings Considering the Interference of the Meteorological Conditions
Dielectric loss on-line monitoring technology is an important means to detect bushing defects and avoid equipment accidents. However
the dielectric loss monitoring data could be affected by meteorological conditions
which might lead to false alarm. In order to reduce the false alarms caused by meteorological factors
this paper analyzes the correlation of porcelain cover oil-impregnated paper bushings’ on-line monitoring data and corresponding meteorological data
and the results show that there is a significant positive correlation between the dielectric loss and rainfall
while the correlation with the temperature and humidity of the environment is not significant; to explain these phenomenon
the author constructs the equivalent circuit model of transformer bushing.Based on the correlativity of rainfall and the dielectric loss monitoring values
three early warning strategies have been proposed to eliminate the interference of rainfall on dielectric loss monitoring data
which are the inter-phase comparison method
the comprehensive method considering meteorological condition and the time-delay method
it is verified by the monitoring data of in operation bushings that the last two methods perform well in excluding the interference caused by rainfall.