SIMA Wenxia, JIANG Xiongwei, PENG Qingjun, et al. Analysis and Protection of Overvoltage of 35 kV Shunt Compensation Capacitor Bank When Relay Protection Take Action[J]. High voltageapparatus, 2017, 53(8): 1-8.
SIMA Wenxia, JIANG Xiongwei, PENG Qingjun, et al. Analysis and Protection of Overvoltage of 35 kV Shunt Compensation Capacitor Bank When Relay Protection Take Action[J]. High voltageapparatus, 2017, 53(8): 1-8. DOI: 10.13296/j.1001-1609.hva.2017.08.001.
Analysis and Protection of Overvoltage of 35 kV Shunt Compensation Capacitor Bank When Relay Protection Take Action
In order to explore the mechanism of overvoltage when vacuum breaker breaking 35 kV shunt capacitors and improve the simulation model
a general review of simulating researches on vacuum circuit breakers switching off shunt capacitors is given. The paper established a three-phase simulation of the VCB switching off shunt capacitors in ATP-EMTP to simulate the field tests based on the models
and cable parasitic parameters is considered in the simulation. The statistics results show that the main reason of such accidents is relay protection take action
virtual closure phenomenon caused by the fluctuation of bus-ground capacitance and multi-phase reignition. Finally
the suppression measures of the overvoltage caused by the breaking shunt capacitors are presented.