XIE Qing, REN Jie, LI Zhiyu, et al. Simulation Study on Electromagnetic Environment of AC Double-circuit Transmission Lines in Heavy Icing Area[J]. High voltageapparatus, 2017, 53(8): 9-16.
XIE Qing, REN Jie, LI Zhiyu, et al. Simulation Study on Electromagnetic Environment of AC Double-circuit Transmission Lines in Heavy Icing Area[J]. High voltageapparatus, 2017, 53(8): 9-16. DOI: 10.13296/j.1001-1609.hva.2017.08.002.
Simulation Study on Electromagnetic Environment of AC Double-circuit Transmission Lines in Heavy Icing Area
With the increasing voltage levels and growing coverage of transmission lines
the problems of electromagnetic environment and icing become worse.However
less attention has been paid to the electromagnetic environment of transmission lines in icing condition. Therefore
a simulation analysis on the electromagnetic environment of 220 kV AC double-circuit transmission lines in heavy icing area is conducted in this study by means of the software SES-Enviro Plus. The effects of the parameters
such as phase distance
split number
conductor diameter
bundle interval and conductor height
on the electromagnetic environment are investigated
and the characteristics of the electromagnetic environments with and without icing condition are compared.The results show that among the four environmental parameters
only electric field intensity is beyond the limit.A conclusion is drawn that the electromagnetic environment becomes worse in icing area
but the effect rules of the parameters on the electromagnetic environment remain the same.In addition
some suggestions for the design of 220 kV AC double-circuit transmission line in heavy icing area are offered in respect of electromagnetic environment.