GONG Xiaoling, FAN Yanfang, ZHONG Xian, et al. Analysis on Security and Stability of ±800 kV Tianzhong UHVDC Sending Grid[J]. High voltageapparatus, 2017, 53(8): 43-48+54.
GONG Xiaoling, FAN Yanfang, ZHONG Xian, et al. Analysis on Security and Stability of ±800 kV Tianzhong UHVDC Sending Grid[J]. High voltageapparatus, 2017, 53(8): 43-48+54. DOI: 10.13296/j.1001-1609.hva.2017.08.008.
Analysis on Security and Stability of ±800 kV Tianzhong UHVDC Sending Grid
In order to analyze the security and stability of Tianzhong UHVDC sending grid
this paper analyzes the influence of different DC operating conditions based on effective short circuit ratio(OESCR)
filter switching and DC single(double)pole lock failure.Then analyzes the impact of frequency adjuster which is at Xinjiang grid on system frequency characteristic;And the influence on UHVDC stability when generator cutting or DC pole blocking faults under the DC isolated operation. The study results show that the operating conditions of the 6 or 8 generators of the DC auxiliary power station can be set up
and the frequency of DC operation is large affected by the frequency adjuster of power grid. But
the DC isolated system frequency stability and transient overvoltage problems are easy to be caused by the DC generator cutting and DC single pole lock failure when considering non control measures. Therefore
it should take stability control strategies or DC power emergency control to enhance the security and stability of the UHVDC system.