Analysis of DC Magnetic Bias Data of Converter Transformer in CSG
The dense distribution of HVDC projects of CSG is concentrated in the China’s Pearl River Delta Region.With the new HVDC projects put into operation
the DC magnetic bias is more prominent caused by the ground return current of grounding electrode.According to the geographical situation of the grounding electrode and the converter station
the principle of the increase of the ground potential is discussed
the mechanism and the damage caused by DC bias magnetic current are analyzed. In order to solve the DC magnetic bias in the operation of the converter station
based on the original transient recording data of the neutral point of the converter transformer
the DC magnetic bias current is calculated. Computational and statistical results show that
with the increase of the ground return current
the DC magnetic bias current of the converter transformer also shows an increasing trend.Thereinto
Congxi Converter Station by the DC magnetic bias current is more serious.When the ground return current of the Yulongling Grounding Electrode rises to 3 558 A
the maximum of the DC bias current of the neutral point of the converter transformer rises to 40 A.Finally
according to the results of statistical data
suggestion for installing a capacitance isolation DC device in transformer neutral point is presented at Congxi Converter Station. The capacitance isolation DC device has been put into operation and achieved good effect of DC isolation.