Study on DC Bias Suppression Measures Based on Multiple Different Transformers
a substation which contains AC transformers and converter transformers is treated as typical example that a substation contains multiple different transformers. In the case of the presence of the bias current
DC bias current in every transformer neutral point distribution is calculated in detail
in which the DC bias current in AC transformers’ neutral point is about 2 times of the DC bias current in converter transformers’ neutral point. The main DC bias suppression measures are briefly introduced
the corresponding suppression measures are applied only to AC transformers which is used to suppress the DC bias in the entire substation. Finally
this paper takes a practical DC project as basis to build in a detailed electromagnetic transient model. The following results can be obtained through simulation: the corresponding suppression measures are only applied to AC transformers can effectively inhibit the DC bias in the entire substation. Considering the variety of factors
the method of connecting series capacitor in the AC transformers’ neutral point is chosen to suppress the DC bias in the entire substation.