Analysis of an Abnormal Voltage Accident of 500 kV Double-circuit Transmission Line on the Same Tower
it will cause damage to electrical equipment and large area of power failure
so it needs to focus on and prevention.In this paper
an abnormal voltage accident of 500 kV double-circuit transmission line on the same tower caused by parametric resonance between high-voltage reactors and capacitive resistance is described.Through analysis of the fault waveform and simulation for fault current and fault voltage
the reason of this accident is verified. Finally
some measures are put forward in order to avoid similar accidents.