WANG Benjin, JIAO Yang, XU Si’en, et al. DC-side Harmonic Voltage Measurement System of Ultra-high Voltage DC Transmission System[J]. High voltageapparatus, 2017, 53(9): 23-29.
WANG Benjin, JIAO Yang, XU Si’en, et al. DC-side Harmonic Voltage Measurement System of Ultra-high Voltage DC Transmission System[J]. High voltageapparatus, 2017, 53(9): 23-29. DOI: 10.13296/j.1001-1609.hva.2017.09.005.
DC-side Harmonic Voltage Measurement System of Ultra-high Voltage DC Transmission System
The measurement of the harmonic voltage on the DC side of an ultra-high voltage DC(UHVDC) transmission system is of significance for design of the DC-side filter and allocation of the relay protection equipment. In this study
taking a ±1 100 kV DC transmission system as an example
the generation and characteristics of the DC-side harmonic voltage were analyzed
and a harmonic voltage measurement scheme was proposed. Consequently
a DC-side harmonic voltage measurement system was built. Then
a test platform was built to assess the accuracy and the frequency response characteristic of the measurement system
and a data processing algorithm was developed. Test result shows that the measurement system
accompanying with the data processing algorithm
can measure the DC-side harmonic voltage in the range from 50 to 1 200 Hz with an amplitude error smaller than 0.5%% and a phase error smaller than 0.5 degree
and it adapts to the frequency fluctuation of power system.