Calculation of Very Fast Transient Overvoltage for 800 kV GIS Substation
The very fast transient overvoltage(VFTO) caused by operation of disconnector in a GIS substation will harm the GIS equipment
the transformer
and the secondary equipment connected with GIS due to its high amplitude. In this study
for design and layout of GIS substation
this paper calculated the parameter of major equipment of a 800 kV GIS substation
and the calculation was verified by measurement. Moreover
EMTP program was adopted to simulate the VFTO generated by disconnector in six different operating modes
thus the maximum values and location of VFTO in the six different operating modes of disconnector were obtained. comparison with the safe criteria indicated that the insulation of the 800 kV GIS substation meets the requirements. In addition