XIA Yanwei, ZHANG Jiantao, XIE Qing. Engineering Calculation Method for Winding Temperature Rise of Oil Immersed Power Transformer[J]. High voltageapparatus, 2017, 53(9): 176-180.
XIA Yanwei, ZHANG Jiantao, XIE Qing. Engineering Calculation Method for Winding Temperature Rise of Oil Immersed Power Transformer[J]. High voltageapparatus, 2017, 53(9): 176-180. DOI: 10.13296/j.1001-1609.hva.2017.09.030.
Engineering Calculation Method for Winding Temperature Rise of Oil Immersed Power Transformer
The winding temperature rise of oil immersed power transformer directly affects the load capacity of the transformer
because the windingtemperature rise test of transformer is of low efficiency and high cost
engineering calculation methods are important for windingtemperature rise of transformer. The existing engineering calculation methods are different without a common standard
resulting in different calculation results or large error. In this paper
a transformer winding model is established
the distribution of oil flow in the winding is analyzed and an engineering calculation methodfor winding temperature rise of transformeris proposed. According to practical condition
the winding temperature rise of a transformer with cooler is calculated with the proposed method under the strong oil guide cooling mode
the results of engineering calculation are compared with the measured results of transformer factory and it shows that the method has less error and can meet the actual needs of the project.