CAO Meigen, GAO Zhengguo, ZHANG Jian, et al. Vibration Fatigue Test and Damage Identification of High-voltage Porcelain Insulator[J]. High voltageapparatus, 2017, 53(10): 7-11+18.
CAO Meigen, GAO Zhengguo, ZHANG Jian, et al. Vibration Fatigue Test and Damage Identification of High-voltage Porcelain Insulator[J]. High voltageapparatus, 2017, 53(10): 7-11+18. DOI: 10.13296/j.1001-1609.hva.2017.10.002.
Vibration Fatigue Test and Damage Identification of High-voltage Porcelain Insulator
High-voltage porcelain insulator is widely used in substation
and the seismic performance is very weak.Through the vibration fatigue test of three same types of post insulators
the relationship between the frequency and the load frequency is obtained.Under the action of long-term cyclic vibration load
although insulator appearance inspection is normal
the damage of the insulator is mainly due to the attenuation of flange bending stiffness
which leads to the decrease of the frequency of the insulator in different degrees.In addition
through the establishment of finite element model test of insulator structure
the first two order frequencies of the vibration modes before and after the loading of the insulator are fitted.The bending stiffness coefficient and other parameters of the insulator flange joints are obtained.This not only describes the damage of insulator