REN Junpeng, WANG Dong, DU Zhiye, et al. Simulation Analysis of 3-D Airflow-temperature Rise for High-voltage Switchgear Under Forced Air Cooling[J]. High voltageapparatus, 2017, 53(10): 12-18.
REN Junpeng, WANG Dong, DU Zhiye, et al. Simulation Analysis of 3-D Airflow-temperature Rise for High-voltage Switchgear Under Forced Air Cooling[J]. High voltageapparatus, 2017, 53(10): 12-18. DOI: 10.13296/j.1001-1609.hva.2017.10.003.
Simulation Analysis of 3-D Airflow-temperature Rise for High-voltage Switchgear Under Forced Air Cooling
three dimensional airflow-temperature rise simulation of 10 kV KYN-28A High-voltage switchgear is analyzed to assist the design and optimization of high voltage switchgear
reduce the test times and shorten the product development cycle.Through the establishment of 3D 10 kV High-voltage switchgear model
mesh and calculation of heating power
the temperature of components in switchgear and air distribution inside are cal culated
using the finite volume method.The calculation results show that the flow velocity of the upper and lower static contact box is obviously different under the forced air cooling condition
and the temperature of the upper isolated contacts are higher than the lower part.The upper isolated contacts are the main heating position.Temperature rise test is carried out and the computational results are basically consistent with experiment.