HUANG Yanguang, LIU Yushun, TIAN Yan, et al. Analysis of Time-domain Characteristic of Ultra-high Frequency Antenna Detecting Partial Discharge[J]. High voltageapparatus, 2017, 53(10): 56-60+67.
HUANG Yanguang, LIU Yushun, TIAN Yan, et al. Analysis of Time-domain Characteristic of Ultra-high Frequency Antenna Detecting Partial Discharge[J]. High voltageapparatus, 2017, 53(10): 56-60+67. DOI: 10.13296/j.1001-1609.hva.2017.10.010.
Analysis of Time-domain Characteristic of Ultra-high Frequency Antenna Detecting Partial Discharge
The analysis of time-domain signal is a significance method of pattern recognition and fault degree identification in partial discharge(PD)detection.Frequency domain parameter is usually used as the performance judgment standard of ultra-high frequency(UHF)detecting antenna.However
this method is unable to judge the impulse response characteristic of UHF antenna in the time-domain.The time-domain characteristics test system of PD UHF detecting antenna based on reciprocity theorem for antenna is built in this paper.Three time domain judgment parameter(oscillation time
correlation coefficient and energy of first waveform)for UHF detecting antenna is proposed in this paper.The time-domain characteristic of four representative ultra-wide band UHF antennas(the ridged horn antenna
the Vivaldi antenna
the micros-trip antenna and the spiral antenna and)has been tested.The results show that the ridged horn antenna and the Vivaldi antenna present the excellent time-domain characteristics and retain the characteristics of signal source maximally.The impulse response test results of four UHF detecting antenna are verified in simulation PD test.The results show that the ridged horn antenna and the Vivaldi antenna are appropriate for PD detecting.
Research on Application of Microphone-optimized Spiral Arrays-based Acoustic Imaging Devices in Partial Discharge Localization
Study on Fiber Interferometric Partial Discharge Ultrasonic Sensing Method Based on Acoustic-optic Modulation and RF Phase Detection
High-frequency Sensing Technology of Partial Discharge of Switchgear Cabinet for Wind Solar & Energy Storage Stations in Gobi Deserts
Research on Influence of Piezoelectric Material Properties and Element Size on Sensitivity of Piezoelectric Sensor for Partial Discharge Monitoring of Transformer
Influence of Environmental Factors on Insulation Performance of Separable Connector for 12 kV Gas Filling Switchgear Cabinet
Related Author
YUE Song
GAO Fei
HAN Shuai
DONG Haoyuan
LI Jun
LI Xin
LIU Chao
QIAO Hui
Related Institution
Electric Power Research Institute of State Grid Tibet Company
China Electric Power Research Institute Co., Ltd.
Iflytek Co., Ltd.
Electric Power Research Institute, State Grid Hebei Electric Power Co., Ltd.
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University