Impulse Test Study on Decreasing Resistance Measures of Typical Grounding Devices of Wind Turbine Generators
Great grounding devices are important measures of thundering prevention of wind turbine generator systems and the impulse characteristics is major index to judge if the grounding devices good or not.In this paper
using the high impulse current generate to simulate the lightning impulse current
conducting impulse characteristics test to the typical grounding conductors of wind turbine generator systems-annulus grounding conductors and its improvements.The concept of the rate of change impulse characteristics is proposed
to quantitatively describe the common affects of spark effect and other impulse properties on the impulse grounding resistance
its value reacts the size of the strength
its symbol reacts the trend.Considering the rate of change impulse characteristics
the results discover that when the soil have two levels that the upper resistance is higher than the lower
adding vertical grounding conductors reaching to the lower soil lever can decrease the impulse grounding resistance apparently
and change the rate of impulse characteristics from -0.36 Ω/kA to-0.07 Ω/kA; When the length of the grounding conductors is stationary
replacing the annulus grounding conductors by the annulus conductors with level branch can decrease the impulse grounding resistance
but more significant is the rate of impulse characteristics change to -0.8Ω/kA.The results have some guidance for the wind turbine grounding device selection.