ZHANG Wenjia, SUN Wentao, CAI Hui, et al. Study on Identification and Optimization for Weak Areas of Static Voltage Stability in DC Multi-infeed Power Grid[J]. High voltageapparatus, 2017, 53(10): 164-169+177.
ZHANG Wenjia, SUN Wentao, CAI Hui, et al. Study on Identification and Optimization for Weak Areas of Static Voltage Stability in DC Multi-infeed Power Grid[J]. High voltageapparatus, 2017, 53(10): 164-169+177. DOI: 10.13296/j.1001-1609.hva.2017.10.027.
Study on Identification and Optimization for Weak Areas of Static Voltage Stability in DC Multi-infeed Power Grid
The DC multi-infeed receiving-end power grid is gradually increasing in the high-voltage transmission system.Serious failure may lead to large-scale power flow transfer
which will impact voltage stability of the receivingend power grid.In serious cases
it will even cause the voltage to collapse.In this paper
a method of weak areas identification using static voltage limit power and node relative participation factor based on continuation power flow
severe failure set and modal analysis is proposed.This method is applied to the southern Jiangsu.A voltage stability optimization measure is put forward.The calculation results show that the weak areas in southern Jiangsu are located in Suzhou power grid and the region of Jinsu UHVDC.The voltage stability of the DC multi-infeed receivingend power grid can be better improved by installing the dynamic reactive power compensation device in the weak areas.