TAO Shiyang, ZHANG Xuezhe, DUAN Dapeng, et al. Research on Transient Earth Voltage Detection Technology for Switchgear Insulation Defects[J]. High voltageapparatus, 2017, 53(10): 215-221.
TAO Shiyang, ZHANG Xuezhe, DUAN Dapeng, et al. Research on Transient Earth Voltage Detection Technology for Switchgear Insulation Defects[J]. High voltageapparatus, 2017, 53(10): 215-221. DOI: 10.13296/j.1001-1609.hva.2017.10.035.
Research on Transient Earth Voltage Detection Technology for Switchgear Insulation Defects
Transient Earth Voltage(TEV)gets more and more used in live detection of switchgears due to high sensitivity
anti-interference ability and non-invasive
etc.This article has independently developed four typical defect models which are insulated air discharge
creeping discharge
floating potential discharge and corona discharge based on fully analysis of fault cases of actual operating switchgear and the actual detection effect of TEV worked out by state grid provincial companies.TEV sensors and TEV handheld tester are used.Analysis of time-domain waveform and PRPD maps of different defects shows that: the sensitivities of TEV on different discharge are different;the discharge capacity
discharge waveform
TEV time-domain waveform and PRPD maps of four types of PD defects has a good identification;when the detection position is different
it shows a certain regularity of the results detected by TEV sensors and TEV handheld tester.It is studied by simulation of CST and tests.Contents of this paper have greater significance on the switchgear periodic general detection and theoretical research of TEV methods.
Research on Partial Discharge Feature Extraction and Type Identification Method of Switchgear Based on Transient Earth Voltage
Application of TEV and Ultrasonic Detection Methods in Partial Discharge Detection of Switchgear
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
Research on the Influence of Temperature and Humidity on the Physical Signal of Partial Discharge of Switchgear
RESEARCH ON THE CHARACTERISTICS OF ULTRASONIC SIGNALS OF PARTIAL DISCHARGE IN 12V SWITCHGEAR CABINET
Related Author
LI Binbin
ZHANG Jian
KE Yanguo
TIAN Yu
YANG Wei
ZHU Shenglong
WANGPeng
LIU Yuting
Related Institution
State Grid Electric Power Research Institute of Anhui Electric Power Co.,Ltd.
State Grid Anhui Electric Power Co., Ltd.
State Grid Jiangxi Power Grid Corporation
Beijing Key Laboratory of High Voltage & Electromagnetic Compatibility, North China Electric Power University
State Grid Jiangxi Electric Power Research Institute