LU Zhumao, LIU Qing, WANG Tianzheng, et al. Comprehensive Application and Research of Multi Live Detection Methods in Partial Discharge Diagnosis for GIS[J]. High voltageapparatus, 2017, 53(10): 222-226+237.
LU Zhumao, LIU Qing, WANG Tianzheng, et al. Comprehensive Application and Research of Multi Live Detection Methods in Partial Discharge Diagnosis for GIS[J]. High voltageapparatus, 2017, 53(10): 222-226+237. DOI: 10.13296/j.1001-1609.hva.2017.10.036.
Comprehensive Application and Research of Multi Live Detection Methods in Partial Discharge Diagnosis for GIS
the problem of partial discharge during operation seriously affects the insulation property of equipment
thus need to strengthen the study of partial discharge detection in GIS.A fault of partial discharge in the 220 kV GIS equipment is analyzed.Combined with several kinds of live detection methods such as ultra-high frequency and acoustic emission partial discharge detection and SF6 gas decomposition test
the partial discharge in the GIS is judged and positioned
while the judgment result of live detection has been proved accurately by disassembling check.The partial discharge fault is caused by failure of equipotential spring.In addition
the GIS partial discharge on-line monitoring information should pay more attention and apply to comprehensive judgment of equipment operation.