LIU Yugen, LI Lixing, XU Xiaoyan, et al. Reconstruction of Substation Grounding Grid Based on Dynamic Neighbor Topology[J]. High voltageapparatus, 2017, 53(11): 15-20+26.
LIU Yugen, LI Lixing, XU Xiaoyan, et al. Reconstruction of Substation Grounding Grid Based on Dynamic Neighbor Topology[J]. High voltageapparatus, 2017, 53(11): 15-20+26. DOI: 10.13296/j.1001-1609.hva.2017.11.003.
Reconstruction of Substation Grounding Grid Based on Dynamic Neighbor Topology
The dynamic topological structure method is introduced to reconstruct the unknown topology of substation grounding grid
thus the solutions to the topology
which satisfy certain threshold distance
are obtained.As a result
the optimal topological structure is obtained via neighbor interconnection.To confirm the reconstruction
a small grounding grid is reconstructed and analyzed.The results show that the mean square voltage of touchable nodes with migration of ground leads is smaller than that without migration when the grounding conductors are equally spaced.Moreover
the abnormal ground leads can be predicted by voltage of nodes.