TONG Tao, GU Danzhen, CUI Yong, et al. Study on Secondary Arc Current of Four-circuit on the Same Tower Lines of AC 1 000 kV and 500 kV/220 kV[J]. High voltageapparatus, 2017, 53(11): 191-196.
TONG Tao, GU Danzhen, CUI Yong, et al. Study on Secondary Arc Current of Four-circuit on the Same Tower Lines of AC 1 000 kV and 500 kV/220 kV[J]. High voltageapparatus, 2017, 53(11): 191-196. DOI: 10.13296/j.1001-1609.hva.2017.11.031.
Study on Secondary Arc Current of Four-circuit on the Same Tower Lines of AC 1 000 kV and 500 kV/220 kV
For four-circuit transmission lines with mixed voltages on the same tower
the electromagnetic interaction between lines is stronger and makes the problem of the secondary arc current complicated.To solve it
the mechanism of the secondary arc current has been discussed
a hybrid tower model that consist of double-circuit1 000 kV lines and double-circuit 500 kV or 220 kV lines has been built in the electromagnetic transient program ATP-EMTP and the secondary arc current and recovery voltage of different voltage lines under different operation modes has been calculated.The results indicate that 500 kV or 220 kV lines have little influence on 1 000 kV lines while the 1 000 kV lines affect the 500 kV or 220 kV lines a lot.Furthermore
this study presents the recomm-ended single-phase reclosing time of different voltages and it can be reference for the design and construction.