MA Xiangnan. Fault Analysis and Measures for Light-triggered Thyristor of ±800 kV Chuxiong Converter[J]. High voltageapparatus, 2017, 53(11): 236-245. DOI: 10.13296/j.1001-1609.hva.2017.11.038.
Fault Analysis and Measures for Light-triggered Thyristor of ±800 kV Chuxiong Converter
Converter valve is the core part of the HVDC systems
and the thyristor
the core components of the converter valve
is the key to achieve rectifier and inverter.The light-triggered thyristor(LTT)of T2563 N80 T-S34 is used in converter valve at ±800 kV Chuxiong Converter Station.LTT has integrated overvoltage protection function with low failure rate.However
from the 22 nd April
that the stage IV of the island commissioning for Yunguang DC system ended
to the 10 th May in 2012
a total of 8 converter valve thyristor had failed.Taking into account that more than one thyristor failed in a short period of time
in this paper
the author describes the basic structure and the compo-nents of the converter valves for ±800 kV Chuxiong converter station;clarifies the conduction principle and failure mechanism of the LTT;combining with the thyristor failure situation
the system transient work condition analysis
parameters comparative analysis of the converter valve and the action analysis of the arrester