ZHANG Chong, ZHANG Xuan, ZHANG Zhifeng. Coordination of DC Circuit Breaker and DC Fault Current Limiter[J]. High voltageapparatus, 2017, 53(12): 26-33+41.
ZHANG Chong, ZHANG Xuan, ZHANG Zhifeng. Coordination of DC Circuit Breaker and DC Fault Current Limiter[J]. High voltageapparatus, 2017, 53(12): 26-33+41. DOI: 10.13296/j.1001-1609.hva.2017.12.005.
Coordination of DC Circuit Breaker and DC Fault Current Limiter
Fast DC circuit breaker is essential equipment for fault removal of DC power grid
however its breaking capacity is insufficient to meet the requirements of DC power grid.Fortunately
the cooperation of current limiter and circuit breaker can effectively improve breaking capacity of the circuit breaker
so as to ensure safe operation of the DC power grid.In this paper
an arc characteristic simulation model of high voltage DC circuit breaker is established by using MATLAB/Simulink according to the principle of the circuit breaker in order to investigate the effects of current limiter on the circuit breaker with respect to the breaking time and transient over-voltage.Subsequently
a model of the resistance-type superconducting fault current limiter(RSFCL)is built according to the superconducting belt model for the purpose of adopting variable resistance to simulate the change of resistance in the superconductivity-losing process of the current limiter
and for further analyzing the effect of the current limiter on the breaking process of the circuit breaker.This work may provide a reference for application of DC superconducting current limiter to DC power grid.