TAN Xiangyu, WEN Tao, LIU Xuandong, et al. Method of Impulse Test for GIS with Docking Way and Impulse Waveform Analysis[J]. High voltageapparatus, 2017, 53(12): 54-60.
TAN Xiangyu, WEN Tao, LIU Xuandong, et al. Method of Impulse Test for GIS with Docking Way and Impulse Waveform Analysis[J]. High voltageapparatus, 2017, 53(12): 54-60. DOI: 10.13296/j.1001-1609.hva.2017.12.009.
Method of Impulse Test for GIS with Docking Way and Impulse Waveform Analysis
The impulse test waveform for GIS with large capacitance is greatly influenced by the circuit inductance
it may influence the impulse waveform front time and decrease the effectiveness of insulation defects detecting.Based on the developed 2 000 kV compact impulse voltage generator
the impulse test method of GIS with docking way is proposed
and the impulse tests for 145 kV and 252 kV GIS are carried out.Using the variable impedance switching section and the hydraulic lifting device
it can connect the voltage output terminal of the impulse voltage generator directly to the reserved docking port of GIS
which can make the circuit compact
reduce the inductance introduced by the high voltage wire
and improve the impulse test waveform quality.Finally
the influence of the circuit inductance on the impulse waveform parameters is analyzed by the simulation.Reducing circuit inductance is the key to solve the problem of standard LI test for equipment with large capacitance.