LI Bin, WANG Tingxiang, ZHANG Changhong, et al. Special Operating Conditions and Structural Design Requirements of the Circuit Breakers for EHV/UHV AC Filters[J]. High voltageapparatus, 2017, 53(12): 87-92.
LI Bin, WANG Tingxiang, ZHANG Changhong, et al. Special Operating Conditions and Structural Design Requirements of the Circuit Breakers for EHV/UHV AC Filters[J]. High voltageapparatus, 2017, 53(12): 87-92. DOI: 10.13296/j.1001-1609.hva.2017.12.014.
Special Operating Conditions and Structural Design Requirements of the Circuit Breakers for EHV/UHV AC Filters
The special operating conditions and switching process of the AFC circuit breaker are introduced.To meet the requirements of the circuit breaker
a special design of arc-extinguishing chamber
which is different from that for other common circuit breakers for line operation and protection
is put forward.In this special design
parallel grading resistor is adopted to improve the potential distributions on both fractures of the chamber
so as to enhance the internal and external insulation reliability of the AFC circuit breaker.A special design of switch-closing resistor is also proposed to reduce the burn of the switch contacts due to switching inrush current and to suppress the electromagnetic vibration.