LEI Min, WANG Quan, FU Jiliang, et al. On-site Calibration Technology of MOA Monitoring Devices[J]. High voltageapparatus, 2017, 53(12): 93-98+105. DOI: 10.13296/j.1001-1609.hva.2017.12.015.
On-site Calibration Technology of MOA Monitoring Devices
Aiming at the problem that the zinc oxide lightning arrester on-site monitoring device is difficult to carry out on-site live calibration
an on-site calibration method with injecting standard signals after emptying leakage current is presented.The corresponding characteristic quantities of the calibration are analyzed
and the measurement standard for on-site monitoring device of zinc oxide arrester is proposed through circuit simulation and analysis on effect of frequency fluctuation on phase fluctuation.Experimental results show that the proposed method and measurement standard can be used for on-site calibration of MOA on-site monitoring device with accuracy of 1% or higher.