Experimental Study on the Safe Distance of Typical Electrode for ±200 kV Converter Station[J]. High voltageapparatus, 2017, 53(12): 112-118. DOI: 10.13296/j.1001-1609.hva.2017.12.018.
Experimental Study on the Safe Distance of Typical Electrode for ±200 kV Converter Station
The existing Chinese specifications and standard do not include the safe distance of ±200 kV voltage class converter station equipment with power.If select a safe distance for ±200 kV voltage class according to that for as high as ±500 kV voltage class
the safety margin is too large.In this article
normal polarity standard operation impact test was conducted for the gaps between five typical electrodes and the other facilities(grounded)in ±200 kV converter station
so the resulting minimum safety distance and risk rate of the typical electrode in the±200 kV converter station were calculated with reference of the related research on live operation.Moreover
considering the range of human activity in the converter station
the minimum safe distance to different typical equipment with power in the ±200 kV converter station was determined as 2.8 m.This research may provide a reference for determination of safe distance to the equipment with power in ±200 kV converter station.