Analysis on a Partial Discharge Defect in GIS Based on On-line Monitoring and Combined Diagnosis
A typical partial discharge defect in GIS was analyzed.This defect was found out by on-line monitoring
and was diagnosed and positioned by the combined technologies of UHF
AE
X-ray
etc.Disassembly inspection showed that one of the two bolts in the No.1 M bus chamber near the B-phase bus’ support insulator has come away from its initial position
and the other has become loose with partial fracture
resulting in floating potential discharge.This paper analyzes the whole procedure of the defect from occurrence to removal for the purposes of illustrating the importance of on-line monitoring and combined diagnosis and providing experience for fault diagnosis of GIS insulation.