Force Analysis of Casing Caused by Over-length Cable in Cable Room of Ring Network Cabinet
European ring network cabinet is widely used in the domestic 10kV distribution network nowadays
but when it is connected with the three-core cable
the casing is always damaged by the bending cable core wire
because the large stress is produced for bending of the overlong cable core wire. In this paper
the force to the casinggenerated by the different lengths and different types of cable core wire is simulated and analyzed based on Ansysfinite element analysis software
and the simulation results is verified through the experimental. The results show thatwhen the core wire is cut too long the force to casing decreased significantly with its height increased. After the test todetermine the allowable loads(500 N) for the casing