Study on VFTO Calculation and Inhibition Method of 550kV GIS Station
The damage of VFTO to the equipment increases with the increase of the rated voltage
and thesuppression of VFTO is of great importance to guarantee the safe operation of the equipment of the GIS substation.Bus design thought
this paper puts forward a kind of damping of the damper bus consists of hollow out solenoid andparallel with the resistance
under power frequency
the insulation performance of busbar
flow capacity andmechanical properties of impact
under the high frequency
the traveling wave current form high voltage through theinductor
the wave energy can be absorbed by the two end damping resistors under the high voltage. This paper setup a typical 550kV GIS station VFTO calculation model
the analysis of the VFTO situation of the main nodes of thesubstation are analyzed under the cases of the 550kV GIS substation maintenance turns 40 kinds of operating modeunder the eight kinds of running condition
the distribution diagram of the maximum VFTO generated bydisconnector operation is obtained. According to the largest VFTO amplitude distribution of busbar equipped withdamping
by the calculation
high amplitude VFTO produced by isolating switch operation times is significantlyreduced
site VFTO most large amplitude reduced from 3.0 p.u. to 2.2 p.u.
and bus bar Ⅰ right end of 3.0 p.u.amplitude reduced to 1.4 p.u.. In this paper
the research results show that the damping bus can effectively reducethe VFTO amplitude and frequency
to reduce caused by VFTO GIS internal equipment
external connectionequipment and secondary equipment safety issues have a significant effect.