Detection and Analysis of Partial Discharge Characteristics for High Voltage Switchgear Internal Electrical Device
There exist many reasons for the partial discharge in switchgear such as the insulation defect
insulationaging
and the lack of insulation gap and so on
so the judgment of partial discharge type is important for theevaluation of switchgear operation status. The internal structure of switchgear is analyzed
the features of differentdetection method are discussed and the decision and location method of partial discharge are given. Base on the 3 cases partial discharge
as for the employed detection method
the amplitude
characteristics
location
types andreason of partial discharge are researched
meanwhile
the sensitivity of the detection method under different cases isalso given. The testing data show that: TEV is more sensitive than AE as for the internal PD of arrester
UHF is moresensitive than TEV and AE as for the internal insulation PD of PT
AE and UHF is more sensitive than TEV as forthe surface PD of wall bushing. The research on the partial discharge characteristics of different electrical equipmentin the switchgear provides important parameters and basis for the condition maintenance of the high voltageswitchgear
and provides powerful technical support for the on-site test personnel.