CAO Jianjun, SUI Bin, YANG Feibao, et al. Quantitative Evaluation Research on Moisture Content and Aging State of Transformer Oil-paper Insulation[J]. High voltageapparatus, 2018, 54(1): 143-151+157.
CAO Jianjun, SUI Bin, YANG Feibao, et al. Quantitative Evaluation Research on Moisture Content and Aging State of Transformer Oil-paper Insulation[J]. High voltageapparatus, 2018, 54(1): 143-151+157. DOI: 10.13296/j.1001-1609.hva.2018.01.021.
Quantitative Evaluation Research on Moisture Content and Aging State of Transformer Oil-paper Insulation
In order to distinguish the influence of aging state and moisture on frequency domain spectroscopy andimprove the accuracy of assessing aging state and moisture content of oil-paper insulation
five groups of oil-paper insulation samples with different agingstate and moisture content are prepared
and then the tanδ spectrum for each group of specimens is performed test.The testing results show that in the bands of 10-3
1
0-1 Hz
the tanδ value increases with aging degree
w
hile in theband of 10-3
1
02 Hz
the tanδ value significantly increases with moisture content
obtains the integral value of Sm andSDPto tanδ curve in feature band of 10-1
1
02 Hz and 10-3
1
0-1 Hz as characteristic parameters to assess moisturecontent and aging state
and establishes quantitative relationship among characteristic parameters moisture content(Kw)and degree of polymerization(DP). Through comparing and analyzing the dielectric loss spectrum
the resultshow that the moisture content in insulating paper had great influence on characteristic parameters SDP. Therefore
inthis paper proposes moisture compensation factor to quantitatively analyze the influence of the moisture content toaging assessment
and further puts forward the new method to assess the aging state of oil-paper insulation whichcomprehensively considering the influence of moisture content in insulating paper.