LEI Hankun, JIA Zhijie. Research on Combined Method of Ultra High Frequency and X-ray Digital Imaging for Detecting Internal Discharge Defects of GIS Solid Insulation[J]. High voltageapparatus, 2018, 54(1): 224-229.
LEI Hankun, JIA Zhijie. Research on Combined Method of Ultra High Frequency and X-ray Digital Imaging for Detecting Internal Discharge Defects of GIS Solid Insulation[J]. High voltageapparatus, 2018, 54(1): 224-229. DOI: 10.13296/j.1001-1609.hva.2018.01.034.
Research on Combined Method of Ultra High Frequency and X-ray Digital Imaging for Detecting Internal Discharge Defects of GIS Solid Insulation
Comparing with ultrasonic partial discharge detection method
ultra high frequency partial discharge de-tection method detects and locates internal discharge defects of GIS solid insulation with good effect
however
be-cause internal discharge defect position and type can not be confirmed
equipment maintenance strategy accordingto this is difficult to ensure perfection and accuracy. So
this article research on combined method of ultra high fre-quency partial discharge and X-ray digital imaging defect detection for detecting internal discharge defects of GISsolid insulation
after solid insulation defects are detected and located by ultra high frequency partial discharge de-tection method
defects can be visual confirmed by X-ray digital imaging during equipment maintenance. In 110kVGIS on-site detection of one 110kV substation. This method successfully detects the electrical tree defect in the in-sulation rod of disconnector in a live detection of 110kV GIS in a 110kV substation
which indicates that the meth-od is helpful to improve the detection and location effect of partial discharge in GIS solid insulation