WU Junhui, BAI Su, YANG Zhiyong, et al. Measurement of Arc Temperature in Nozzle of SF6 Circuit Breaker During Heavy Current Interruptions[J]. High voltageapparatus, 2018, 54(2): 7-11+19.
WU Junhui, BAI Su, YANG Zhiyong, et al. Measurement of Arc Temperature in Nozzle of SF6 Circuit Breaker During Heavy Current Interruptions[J]. High voltageapparatus, 2018, 54(2): 7-11+19. DOI: 10.13296/j.1001-1609.hva.2018.02.002.
Measurement of Arc Temperature in Nozzle of SF6 Circuit Breaker During Heavy Current Interruptions
Investigation is performed on the method of arc temperature measurement in SF
6
circuit breaker’s nozzleduring heavy current interruptions. Tests are conducted with a 126 k V SF
6
circuit breaker;the measurement is imple-mented by means of spectral method to obtain the spectral line intensity of CuⅠ510.5 nm
CuⅠ515.3 nm and CuⅠ521.8 nm. By using relative intensities lines method obtain the arc temperature. In order to measure the spatial distri-bution of arc temperature effectively
the nozzle is replaced with a transparent organic glass material from a
PTFEmaterial
which leads temperature axial distribution of the arc is effectively obtained. Measurement is performed ateach interval 1 ms during the whole operating process
which obtains the variation low of arc temperature with time.The temperature measurement method established is effective for measuring the temperature variation in the wholeoperating process.