KANG Jun, LI Qiuyang, LI Yuan, et al. Wave Process Simulation Analysis of 1 100 kV GIS Under Oscillation Impulse Testing Voltages[J]. High voltageapparatus, 2018, 54(2): 20-25+32.
KANG Jun, LI Qiuyang, LI Yuan, et al. Wave Process Simulation Analysis of 1 100 kV GIS Under Oscillation Impulse Testing Voltages[J]. High voltageapparatus, 2018, 54(2): 20-25+32. DOI: 10.13296/j.1001-1609.hva.2018.02.004.
Wave Process Simulation Analysis of 1 100 kV GIS Under Oscillation Impulse Testing Voltages
In the process of field impulse voltage withstand test of UHV GIS(gas insulated switchgear)
electromag-netic waves in GIS affected by oscillatory surge voltage are prone to refraction and reflection
and that will causes thevoltage waves superposition may higher than the test voltage required by the standard
endangering GIS insulation.To effectively evaluate the GIS overvoltage in case of oscillatory surge
the impulse voltage test method is optimized.The voltage distribution of each GIS node of is obtained by utilizing EMTP simulation software
based on field test pa-rameters
for the simulation of and analysis on the wave process in two different conditions
normal impulse with-stand voltage of GIS and flashover of GIS in the test process. The results show that GIS nodes demonstrated similarvoltage without noticeable wave process in case of normal oscillatory surge of GIS. However
in case of internal flash-over
the end node voltage of GIS branch affected by the cut-off voltage waves would greatly exceed the test voltage
triggering secondary flashover. In consideration of this case
feasible suppression measures are proposed on the basisof simulation calculation and in combination with actual conditions
which provides a technical basis for the field im-pulse voltage test of 1 100 k V GIS equipment in the future.