BAN Jian, GAO Xiangxiang, HUANG Shi, et al. Study on the Calculation Method of TRV Waveform Envelope and Standard Value Parameter Based on Coordinate System Conversion[J]. High voltageapparatus, 2018, 54(2): 46-49.
BAN Jian, GAO Xiangxiang, HUANG Shi, et al. Study on the Calculation Method of TRV Waveform Envelope and Standard Value Parameter Based on Coordinate System Conversion[J]. High voltageapparatus, 2018, 54(2): 46-49. DOI: 10.13296/j.1001-1609.hva.2018.02.008.
Study on the Calculation Method of TRV Waveform Envelope and Standard Value Parameter Based on Coordinate System Conversion
The transient recovery voltage(TRV)standard value parameters are an important indicator for the shortcircuit breaking test of high voltage circuit-breakers at the high power test station. This paper presents a calculationmethod of TRV waveform envelope and standard value parameters
which is converted the TRV waveform data fromthe Cartesian coordinate system to the polar coordinate system
and gain three straight lines of two-parameters TRVor four straight lines of four-parameters TRV tangent to the TRV waveform and the TRV standard parameter value bycalculated the TRV waveform data in the polar coordinate system. The TRV standard value parameters are obtainedby this calculation method
which can provide the theory basis for adjusting the R
L and C parameters of the test cir-cuit
and provide the theory basis for reading and evaluation the TRV parameters after the test when proceeding short-circuit breaking test at the high power station.