JI Binwei, GU Yonggang, LIU Zirui, et al. Research on Ultra-high-voltage GIS On-site Lightning Impulse Withstand Voltage Test Transient Over-voltage and Its Restraining Method[J]. High voltageapparatus, 2018, 54(2): 76-83.
JI Binwei, GU Yonggang, LIU Zirui, et al. Research on Ultra-high-voltage GIS On-site Lightning Impulse Withstand Voltage Test Transient Over-voltage and Its Restraining Method[J]. High voltageapparatus, 2018, 54(2): 76-83. DOI: 10.13296/j.1001-1609.hva.2018.02.013.
Research on Ultra-high-voltage GIS On-site Lightning Impulse Withstand Voltage Test Transient Over-voltage and Its Restraining Method
导致此类节点处出现幅值高于2 400 k V的高幅值过电压;参数取值为Cr=800 p F、Rr=100Ω的弱阻尼暂态过电压抑制器能够有效抑制2台断路器串联与接入3台断路器方式下空载套管顶端的高幅值过电压
且对未发生放电时的雷电冲击试验电压影响极小
具备应用于现场试验的可行性。
Abstract
Gas insulated switchgear(GIS)has been widely used in electrical power system.During the on-site light-ning impulse withstand voltage test of GIS
when the underproof GIS discharges
high-amplitude oscillating over-voltage will take place
which may threaten the intact equipments. In this paper
we developed a ATP-EMTP tran-sient analyzing model of ultra-high-voltage GIS on-site lightning impulse withstand voltage test system and fault arc.The over-voltage amplitude and its restraining method has been investigated. The results show that the calculatedvoltage waveforms matches well with the test waveforms
indicating that the fault arc model can simulate the dis-charging process accurately. The fringe nodes in the test system will cause the total reflection of transient voltage
making the over-voltage amplitude higher than 2 400 k V. The over-voltage amplitude on top of the no-load bushingcan be restrained after the introduction of the low-damping transient voltage restrainer. The parameter Cr=800 p F、Rr=100 Ω is suggested
which can effectively make the oscillating voltage lower than 2 400 k V.
Transient Over-voltage Online Monitoring Technology Based on 500 kV Capacitive Voltage Transformer with Interior Low-voltage Capacitor C3
Simulation Study on Transient Over-voltage in Power Collection Network of Offshore Wind Farm Considering Prestrike Characteristics of Vacuum Circuit Breaker
Research on Step Wave Generator with Nanosecond Rising Edge for Calibration of External Transient Voltage Sensor
Analysis of New Grounding Mode for Neutral Point of Giant Hydro-generator
Related Author
SI Wenrong
HE Lin
JIN Heng
YANG Linghui
LIU Zhaolin
FU Chenzhao
WU Junchen
GUO Yaxun
Related Institution
Electric Power Research Institute,SMEPC
East China Electric Power Co.,Ltd.
School of Information Engineering,Xiangtan University
Guangzhou Bureau,EHV Power Transmission Company of China Southern Grid